Giganet 25kVA/25kW 3-Phase Online Double Conversion UPS
The Giganet 25 kVA / 25 kW 3-Phase Online Double Conversion UPS is a high-capacity, enterprise-grade power protection system designed for mission-critical environments. Built on true online double-conversion topology, it delivers clean, uninterrupted, fully regulated AC power — regardless of fluctuations or disturbances in the mains supply.
This makes it ideal for data centers, server farms, telecom installations, industrial facilities, or any heavy load infrastructure where uptime, stability, and equipment protection are non-negotiable.
Features |
| Double conversion online design |
| Input power factor correction (PFC) technology, input power factor up to 0.99 |
| Digital signal process (DSP) makes the system more stable and reliable |
| Parallel cabinet is not required, it can be paralleled directly; 10~30kVA can be paralleled by 4 sets, 40~50kVA by 6 sets |
| LBS synchronization (40~50kVA) |
| Battery pack can be common connection in parallel operation |
| 30~50 pcs batteries are settable |
| Suitable for complete unbalanced load |
| Users can set the charging current, constant current, constant voltage and floating charging three-stage charging management automatic smooth switch |
| Output overload, output short circuit, inverter over temperature, battery under voltage warning and battery overcharge protection |
| Static electronic bypass switches |
| DC start function. |
| Fan intelligent speed regulation design, prolong fan life, high efficiency and energy saving. |
| EPO (Emergency Power Off) function |
| LED+LCD Display |
Specifications
| Capacity | 10kVA/10kW | 15kVA/15kW | 20kVA/20kW | 25kVA/25kW | 30kVA/30kW | 40kVA/40kW | 50kVA/50kW | |
| INPUT | ||||||||
| Nominal voltage | 380/400/415Vac, (3Ph+N+PE) | |||||||
| Operating voltage range | 138~485Vac | |||||||
| Operating frequency range | 40Hz~70Hz | |||||||
| Power factor | ≥0.99 | |||||||
| Harmonic distortion (THDi) | ≤3% Linear load | |||||||
| Bypass voltage range | Max.voltage:220V:+25% (Optional+10%,+15%,+20%) 230V:+20% (Optional+10%,+15%)240V:+15% (Optional+10%)
Min.voltage:-45% (Optional-10%,-15%,-20%,-30%) |
|||||||
| Frequency synchronize tracing range | ±10% | |||||||
| Generator input | Support | |||||||
| OUTPUT | ||||||||
| Output voltage | 380/400/415Vac (3Ph+N+PE) | |||||||
| Voltage regulation | ±1% | |||||||
| Power factor | 1.0 | |||||||
| Outputfrequency | Line Mode | ±1%/±2%/±4%/±5%/±10% of the rated frequency (Optional) | ||||||
| Bat. Mode | (50/60±0.1%)Hz | |||||||
| Crest factor | 3:1 | |||||||
| Harmonic distortion (THDv) | ≤2% with linear load≤5% with non linear load | ≤2% with linear load≤4% with non linear load | ||||||
| Overload | Load≤110%: last 60min,≤125%: last 10min,≤150%: last 1min | |||||||
Efficiency |
||||||||
| Efficiency | up to 95.5% | |||||||
| BATTERY | ||||||||
| Battery voltage | Optional Voltage: ±180V/±192V/±204V/±216V/±228V/±240/±252/±264/±276/±288/±300Vdc (30/32/34/36/38/40/42/44/46/48/50pcs optional) 360Vdc~600Vdc (30~50pcs, 30pcs default, 36~50pcs no power derating;32~34pcs output power factor 0.9; 30pcs output power factor 0.8) | |||||||
| Charge Current(A) | 18A Max. | 20A Max. | ||||||
| SYSTEM FEATURES | ||||||||
| Transfer time | Utility to Battery: 0ms; Utility to Bypass: 0ms | |||||||
| Alarm | overload, utility abnormal, UPS fault, battery low, etc. | |||||||
| Backfeed | Support | |||||||
| Protection | short circuit, overload, over temperature, battery low, fan fault alarm | |||||||
|
Communication |
USB, RS232, RS485, Parallel port, Dry contact port, REPO port, Backfeed port, SNMP card (Optional), Battery temperature sensor (Optional) |
REPO port, LBS port, Dry contact port (Backfeed/Battery breaker driver), SNMP card (Optional), Relay card (Optional), Battery temperature sensor (Optional) | ||||||
| ENVIRONMENTAL | ||||||||
| Operating temperature | 0℃~40℃ | |||||||
| Storage temperature | -25℃~55℃(No battery) | |||||||
| Humidity range | 0~95% (Non condensing) | |||||||
| Altitude | <1500m, derating required when>1500m | |||||||
| Noise level | <55dB | <56dB | <58dB | |||||
| PHYSICAL | ||||||||
| Dimension W×D×H (mm) | 440×670×130 (3U) | 440×800×175 (4U) | ||||||
| Net weight (kg) | 25 | 27 | 28 | 45 | 48 | |||
| STANDARDS | ||||||||
| Safety | IEC/EN 62040-1, IEC/EN 62477-1 | |||||||
| EMC | IEC/EN 62040-2 (IEC 61000-2-2, IEC 61000-4-2, IEC 61000-4-3, IEC 61000-4-4, IEC 61000-4-5, IEC 61000-4-6, IEC 61000-4-8, IEC 61000-4-11) | |||||||






Reviews